E-mail: info@solidecking.com
tel-phone:86-21-63803633
Address:Room 103, Jinfeng Building, No. 31 Hengfeng Road, Jing'an District, Shanghai
Mobile phone:13816755915 ©2016 Leshang Technologies Co., Ltd.
ANSI/SDI-RD1.0 Standard for Steel Roof Deck 2
Design:
A. The deck shall be selected by the designer to provide the load capabilities shown on the drawings (design live and dead loads and the SDI construction
loads).
1. The section properties of the steel roof unit deck shall be computed in accordance with the North American Specification for the Design
of Cold-Formed Steel Structural Members.
2. Allowable Stress Design (ASD): Bending stress shall not exceed 0.60 times the yield strength with a maximum of 36 ksi (250 MPa) under the combined dead and design live loads.
3. Load and Resistance Factor Design (LRFD): The load factors are defined in the
governing code. ASCE 7 (See section 1.2.A.5) shall be used in the absence of a governing code. The resistance factors and nominal resistances shall be determined in accordance with the North American Specification for the Design of Cold-Formed Steel Structural Members.
4. Deck Deflection: Deflection of the deck shall not exceed 1/240 of the span (centerline to centerline) or 1 inch (25 mm), whichever is less, under the uniformly
distributed design live load. All spans are to be considered center-to-center of supports.
Commentary: The adequacy of deck edge support details should be reviewed by the designer. At the building perimeter or any other deck termination or direction change, occasional concentrated loading of the roof deck could result in
temporary differences in deflection between the roof deck and the adjacent stationary building component. Supplemental support such as a perimeter angle may be warranted.
5. Suspended Loads: All suspended loads shall be included in the analysis and
calculations for stress and deflection.
Commentary: The designer must take into account the sequence of loading. Suspended loads may include ceilings, light fixtures, ducts or other utilities. The
designer must be informed of any loads applied after the roofing has been installed.
6. Construction and Maintenance Loads: Deck shall be selected by the designer to provide a minimum 30 lbs/sq.ft. (1.44 kPa) construction load. Span lengths shall be
governed by a maximum stress of 0.7 Fy and a maximum deflection of 1/240 of the span with a 200-pound (0.89 kN) concentrated load at midspan on a 1 foot (300 mm) wide section of deck. If the designer contemplates loads of greater magnitude, spans shall be decreased or the thickness of the steel deck increased as required. All loads shall be distributed by appropriate means to prevent damage to the completed assembly during construction.
7. Cantilever loads: The cantilever span shall be determined by the lowest
value considering,
(a) construction phase load of 10 psf (0.48 kPa) on adjacent
span and cantilever, plus 200 pound load (0.89 kN) at end of cantilever with a stress limit of 0.7 Fy (ASD),
(b) a service load of 45 psf (2.15 kPa) on adjacent span and cantilever, plus 100 pound load (0.44 kN) at end of cantilever with a stress limit of 0.6 Fy (ASD), or
(c) with service loads, a deflection limitation of 1/240 of adjacent span for interior
span and deflection limitation at end of cantilever of 1/120 of overhang.
Commentary: Under Construction and Maintenance Loads, and Cantilever Loads, 0.7 Fy maximum stress was selected to unify the ASD and LRFD values. Apply a load factor of 1.4 to 200 pound load when LRFD is used.
ROOF15
8. Diaphragm Shear Capacity: Roof deck shear capacity shall be determined in
accordance with the SDI Diaphragm Design Manual or from tests conducted by an
independent professional engineer.
Commentary: Calculations of diaphragm strength and stiffness should be made using the SDI Diaphragm Design Manual. If testing is used as the means for
determining the diaphragm strength and stiffness, then it should follow the AISI TS 7-02 test protocol.
B. Load Tables: Uniform loads determined for published tables shall be based on equal adjacent two and three span conditions and on single spans. Appropriate
combinations of shear and bending shall be made to determine the published loads. Lengths of 1-1/2 inches (38 mm) for end bearing and 4 inches (100 mm) for interior bearing shall be used to check web crippling. Deflection coefficients
shall be 0.013 for single spans, 0.0054 for double spans and 0.0069 for triple spans.
Commentary:
For deck layouts that provide more than three equal spans, the user can apply
the loads published for three spans. Published uniform load tables do not apply for adjacent spans that differ in length by more than 10%.
Accessories:
A. Ridge and valley plates, and flat plates at change of deck direction shall be furnished as shown on plans to provide a flat (finished) surface for the application of roof insulation and roof cover.
B. Sump pans shall be furnished to receive roof drains as shown on plans. Holes for drains are to be field cut (by others) in the field.
C. Mechanical fasteners or welds shall be permitted for deck and accessory attachment.
E-mail: info@solidecking.com
tel-phone:86-21-63803633
Address:Room 103, Jinfeng Building, No. 31 Hengfeng Road, Jing'an District, Shanghai
Mobile phone:13816755915 ©2016 Leshang Technologies Co., Ltd.