Installation/Anchorage:
A. Form deck units shall be anchored to steel supporting members including perimeter support steel and/or bearing walls by arc spot puddle welds of the following diameter and spacing, fillet welds of equal strength, or mechanical fasteners.
1. All welding of deck shall be in accordance with ANSI/AWS D1.3, Structural Welding Code Sheet Steel. Each welder shall demonstrate an ability to produce satisfactory welds using a procedure such as shown in the SDI Manual of Construction with Steel Deck, or as described in ANSI/AWS D1.3.
2. Welding washers shall be used on all deck units with metal thickness less than 0.028 inches (0.7 mm). Welding washers shall be a minimum thickness of 0.0598 inches (16 gage, 1.50 mm) and have a nominal 3/8 inch (10 mm) diameter hole.
3. Where welding washers are not used, a minimum visible 5/8 inch (15 mm) diameter arc puddle weld shall be used. Weld metal shall penetrate all layers of deck material at end laps and shall have good fusion to the supporting members.
4. Weld spacing: Fastening pattern shall allow slabs to be designed on a continuous basis.
5. When used, fillet welds shall be at least 1-1/2 inch (38 mm) long.
6. Mechanical fasteners, either powder actuated, pneumatically driven, or screws, shall be permitted in lieu of welding to fasten deck to supporting framing if fasteners meet all project service requirements. When the fasteners are powder actuated or pneumatically driven, the load value per fastener used to determine the maximum fastener spacing shall be based on a minimum structural support thickness of not less than 1/8 inch (3 mm) and on the fastener providing a minimum 5/16 inch (8 mm) diameter bearing surface (fastener head size). When the structural support thickness is less than 1/8 inch (3 mm), powder actuated or pneumatically driven fasteners shall not be used, but screws are acceptable.
Commentary: Mechanical fasteners (powder actuated, screws, pneumatically driven fasteners, etc.) are recognized as viable anchoring methods, provided the type and spacing of the fastener satisfies the design criteria. Documentation in the form of test data, design
calculations, or design charts should be submitted by the fastener manufacturer as the basis for obtaining approval.
7. For deck units with spans greater than five feet (1.5 m), side laps and perimeter edges of units between span supports shall be fastened at intervals not exceeding 36 inches (1 m) on center, using one of the following methods: a. #10 self drilling screws.
b. Crimp or button punch.
c. Arc puddle welds 5/8 inch (15 mm) minimum visible diameter, or minimum 1 inch (25 mm) long fillet weld.
Commentary: The above side lap spacing is a minimum. Service loads or diaphragm design may require closer spacing or larger side lap welds. Good metal to metal contact is necessary for a good side lap weld. Burn holes are to be expected.
B. Accessory Attachment:
1. Pour Stop and Girder Fillers: Pour stops and girder fillers shall be fastened to supporting structure in accordance with the SDI Standard Practice Details, and Attachment NC2.
2. Floor Deck Closures: Column closures, cell closures, and Z closures shall be fastened to provide tight fitting closures at open ends of ribs and sides of decking. Fasten cell closures at changes of direction of floor deck units unless otherwise directed.
Commentary: Cell closures are generally not used on form deck of1-5/16inch(33mm) depth or less.